heming28
級別: 略有小成
|
我有一臺三菱A2USCPU報錯,聯線診斷后錯誤代號(D9008) 11,詳細錯誤代號(D9091) 114 我在線清除PLC內存,還是出錯,格式化PLC的內存是灰色,無法執行,程序重新下載也報錯,測電池電壓正常,請問是CPU有問題嗎?, |
---|---|
|
andy003
級別: 網絡英雄
|
Error code list[Error code11,Detailed error code114] Applicable machine AnA,AnU,A2US(H) ===================================================================================== Error code(D9008) 11 Detailed error code(D9091) 114 Error message PARAMETER ERROR [Checked at power on and at STOP/PAUSE -> RUN.] Error and cause Sum check error Corrective action Read parameters in the PLC memory, check the contents, make necessary corrections and write them again to the memory. 后面使用哪些模組? |
---|---|
|